EasyManua.ls Logo

Siemens SIPROTEC 4 7VK61 - Interface Modules

Siemens SIPROTEC 4 7VK61
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
former and additionally the common jumper X60. The jumper X64 determines the rated current for the input
I
E
and may thus have a setting that deviates from that of the phase currents. Jumper X64 is not relevant.
Jumper X64 is plugged in position "IE".
Jumpers X71, X72 and X73 on the input/output board C-I/O-11 are used for setting the bus address and must
not be changed. The following Table lists the jumper presettings.
Table 3-17 Jumper settings of Bus Address of the input/output board C-I/O-11
Jumper Default Setting
X71 1-2 (H)
X72 1-2 (H)
X73 2-3 (L)
Interface Modules
Exchanging Interface Modules
The interface modules are located on the processor board C-CPU-2 (Serial. No 1 in Figure Figure 3-3 to
Figure 3-4).
3.1.2.4
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7VK61, Manual 195
C53000-G1176-C159-5, Edition 05.2018

Table of Contents