Information List
Indications for IEC60870-5-103 are always reported ON / OFF if they are subject to general interrogation for
IEC60870-5-103. If not, they are reported only as ON.
New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to ON/OFF and subjected to
general interrogation if the information type is not a spontaneous event (“.._Ev”). Further information on indi-
cations can be found in detail in the SIPROTEC 4 System Description, Order No. E50417-H1100-C151.
In columns “Event Log”, “Trip Log” and“Ground Fault Log” the following applies:
UPPER CASE NOTATION ON/OFF: definitely set, not allocatable
lower case notation “on/off”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
In column “Marked in Oscill.Record” the following applies:
UPPER CASE NOTATION M: definitely set, not allocatable
lower case notation M: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
- Test mode (Test mode) Device IntS
P
O
N
OF
F
* * LED BO 94 21 1 Yes
- Stop data transmission
(DataStop)
Device IntS
P
O
N
OF
F
* * LED BO 94 20 1 Yes
- Unlock data transmission
via BI (UnlockDT)
Device IntS
P
* * *
- Reset LED (Reset LED) Device IntS
P
O
N
* * LED BO 94 19 1 No
- Clock Synchronization
(SynchClock)
Device IntS
P_E
v
* * * LED BO
- >Back Light on (>Light
on)
Device SP O
N
OF
F
* * BI
- Hardware Test Mode
(HWTestMod)
Device IntS
P
O
N
OF
F
* * LED BO
E.3
Functions, Settings, Information
E.3 Information List
308 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018