Addr. Parameter Function C Setting Options Default Setting Comments
3921 End Flt. stage Breaker Failure ON
OFF
OFF End fault protection
3922 T-EndFault Breaker Failure 0.00 .. 30.00 sec 2.00 sec Trip delay of end fault
protection
3931 PoleDiscrepancy Breaker Failure ON
OFF
OFF Pole Discrepancy supervi-
sion
3932 T-PoleDiscrep. Breaker Failure 0.00 .. 30.00 sec 2.00 sec Trip delay with pole
discrepancy
4001 FCT TripSuperv. TripCirc.Superv ON
OFF
OFF TRIP Circuit Supervision is
4002 No. of BI TripCirc.Superv 1 .. 2 2 Number of Binary Inputs
per trip circuit
4003 Alarm Delay TripCirc.Superv 1 .. 30 sec 2 sec Delay Time for alarm