storage criterion has reset. The maximum recording duration to each fault MAX. LENGTH is set at address
410.
The fault recording can also be triggered via a binary input, via the keypad on the front of the device or with a
PC via the operation or service interface. The storage is then dynamically triggered. The length of the fault
recording is set in address 415 BinIn CAPT.TIME (maximum length however is MAX. LENGTH, address
410). Pre-fault and post-fault times will be included. If the binary input time is set for ∞ , then the length of
the record equals the time that the binary input is activated (static), or the MAX. LENGTH setting in address
410, whichever is shorter.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
Addr. Parameter Setting Options Default Setting Comments
402A WAVEFORMTRIGGER Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
403A WAVEFORM DATA Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
410 MAX. LENGTH 0.30 .. 5.00 sec 2.00 sec Max. length of a Waveform
Capture Record
411 PRE. TRIG. TIME 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to
Trigger
412 POST REC. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME 0.10 .. 5.00 sec 0.50 sec Capture Time via Binary Input
Information List
No.
Information Type of
Informa-
tion
Comments
- FltRecSta IntSP Fault Recording Start
4 >Trig.Wave.Cap. SP >Trigger Waveform Capture
30053 Fault rec. run. OUT Fault recording is running
Ethernet EN100-Module
Functional Description
An Ethernet EN100-Modul allows to integrate the 7VK61 into 100 Mbit communication networks used by
process control and automation systems in accordance with IEC 61850. This standard provides consistent
inter-relay communication without gateways or protocol converters. This allows open and interoperable use of
SIPROTEC 4 devices even in heterogeneous environments. In parallel to the process control integration of the
device, this interface can also be used for communication with DIGSI and for inter-relay communication via
GOOSE.
Setting Notes
Interface selection
No settings are required for operation of the Ethernet system interface module (IEC 61850 Ethernet EN100-
Modul). If the device is equipped with such a module (see MLFB), the module is automatically configured to
the interface available for it.
2.1.6.3
2.1.6.4
2.1.7
2.1.7.1
2.1.7.2
Functions
2.1 General
42 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018