Addr. Parameter C Setting Options Default Setting Comments
2634 I-STUB Telep/BI NO
YES
NO Instantaneous trip via Tele-
prot./BI
2635 I-STUB SOTF NO
YES
NO Instantaneous trip after
SwitchOnToFault
2640 Ip> 1A 0.10 .. 4.00 A 2147483647 A Ip> Pickup
5A 0.50 .. 20.00 A 2147483647 A
2642 T Ip Time Dial 0.05 .. 3.00 sec 0.50 sec T Ip Time Dial
2643 Time Dial TD Ip 0.50 .. 15.00 5.00 Time Dial TD Ip
2646 T Ip Add 0.00 .. 30.00 sec 0.00 sec T Ip Additional Time Delay
2650 3I0p PICKUP 1A 0.05 .. 4.00 A 2147483647 A 3I0p Pickup
5A 0.25 .. 20.00 A 2147483647 A
2652 T 3I0p TimeDial 0.05 .. 3.00 sec 0.50 sec T 3I0p Time Dial
2653 TimeDial TD3I0p 0.50 .. 15.00 5.00 Time Dial TD 3I0p
2656 T 3I0p Add 0.00 .. 30.00 sec 0.00 sec T 3I0p Additional Time
Delay
2660 IEC Curve Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
2661 ANSI Curve Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
2670 I(3I0)p Tele/BI NO
YES
NO Instantaneous trip via Tele-
prot./BI
2671 I(3I0)p SOTF NO
YES
NO Instantaneous trip after
SwitchOnToFault
2680 SOTF Time DELAY 0.00 .. 30.00 sec 0.00 sec Trip time delay after SOTF
Information List
No.
Information Type of
Informa-
tion
Comments
7104 >BLOCK O/C I>> SP >BLOCK Backup OverCurrent I>>
7105 >BLOCK O/C I> SP >BLOCK Backup OverCurrent I>
7106 >BLOCK O/C Ip SP >BLOCK Backup OverCurrent Ip
7110 >O/C InstTRIP SP >Backup OverCurrent InstantaneousTrip
7130 >BLOCK I-STUB SP >BLOCK I-STUB
7131 >I-STUB ENABLE SP >Enable I-STUB-Bus function
7151 O/C OFF OUT Backup O/C is switched OFF
7152 O/C BLOCK OUT Backup O/C is BLOCKED
7153 O/C ACTIVE OUT Backup O/C is ACTIVE
7161 O/C PICKUP OUT Backup O/C PICKED UP
7162 O/C Pickup L1 OUT Backup O/C PICKUP L1
2.3.5
Functions
2.3 Overcurrent protection (optional)
SIPROTEC 4, 7VK61, Manual 81
C53000-G1176-C159-5, Edition 05.2018