No. Description Function IEC 60870-5-103 Configurable in
Matrix
Type
information number
Compatibility
Data Unit
Position
CFC
Control Display
Default Display
601 I L1 (IL1 =) Measurement 94 148 No 9 1 CFC CD DD
134 124 No 9 1
602 I L2 (IL2 =) Measurement 94 148 No 9 2 CFC CD DD
134 124 No 9 2
603 I L3 (IL3 =) Measurement 94 148 No 9 3 CFC CD DD
134 124 No 9 3
610 3I0 (zero sequence) (3I0 =) Measurement 134 124 No 9 14 CFC CD DD
619 I1 (positive sequence) (I1 =) Measurement - - - - - CFC CD DD
620 I2 (negative sequence) (I2 =) Measurement - - - - - CFC CD DD
621 U L1-E (UL1E=) Measurement 94 148 No 9 4 CFC CD DD
134 124 No 9 4
622 U L2-E (UL2E=) Measurement 94 148 No 9 5 CFC CD DD
134 124 No 9 5
623 U L3-E (UL3E=) Measurement 94 148 No 9 6 CFC CD DD
134 124 No 9 6
624 U L12 (UL12=) Measurement 134 124 No 9 10 CFC CD DD
625 U L23 (UL23=) Measurement 134 124 No 9 11 CFC CD DD
626 U L31 (UL31=) Measurement 134 124 No 9 12 CFC CD DD
627 Uen (Uen =) Measurement 134 118 No 9 1 CFC CD DD
631 3U0 (zero sequence) (3U0 =) Measurement - - - - - CFC CD DD
632 Measured value Usy2 (Usy2=) Measurement - - - - - CFC CD DD
633 Ux (separate VT) (Ux =) Measurement - - - - - CFC CD DD
634 U1 (positive sequence) (U1 =) Measurement - - - - - CFC CD DD
635 U2 (negative sequence) (U2 =) Measurement - - - - - CFC CD DD
636 Measured value U-diff (Usy1-
Usy2) (Udiff =)
Measurement 130 1 No 9 2 CFC CD DD
637 Measured value Usy1 (Usy1=) Measurement 130 1 No 9 3 CFC CD DD
638 Measured value Usy2 (Usy2=) Measurement 130 1 No 9 1 CFC CD DD
641 P (active power) (P =) Measurement 94 148 No 9 7 CFC CD DD
134 124 No 9 7
642 Q (reactive power) (Q =) Measurement 94 148 No 9 8 CFC CD DD
134 124 No 9 8
643 Power Factor (PF =) Measurement 134 124 No 9 13 CFC CD DD
644 Frequency (Freq=) Measurement 94 148 No 9 9 CFC CD DD
134 124 No 9 9
645 S (apparent power) (S =) Measurement - - - - - CFC CD DD
646 Frequency fsy2 (F-sy2 =) Measurement 130 1 No 9 4 CFC CD DD
647 Frequency difference (F-diff=) Measurement 130 1 No 9 5 CFC CD DD