>CB1 3p Closed
(No. 410) for the series connection of the NO auxiliary contacts of the CB,
>CB1 3p Open
(No. 411) for the series connection of the NC auxiliary contacts of the CB,
>CB1 Pole L1
(No. 366) for the auxiliary contact of pole L1,
>CB1 Pole L2
(No. 367) for the auxiliary contact of pole L2,
>CB1 Pole L3
(No. 368) for the auxiliary contact of pole L3,
Open Pole Detektor
Besides the evaluation of the CB auxiliary contacts, single-pole dead times can be detected and reported via
the Open Pole Detector. This, however, requires the three-pole connection of currents and voltages. The corre-
sponding protection and monitoring function can respond. The following figure shows the logic structure of
an Open Pole Detector.
2.8.1.3
Functions
2.8 Function Control and Circuit Breaker Test
SIPROTEC 4, 7VK61, Manual 153
C53000-G1176-C159-5, Edition 05.2018