Binary output default settings
Table D-4 Further output relay presettings for 7VK610
Binary Output Allocated Function Indication no. Description
BO1 Relay PICKUP 501 Relay PICKUP
BO2 Relay TRIP 511 Relay GENERAL TRIP command
BO3 Alarm Sum Event 160 Alarm Summary Event
BO4 BF T2-TRIP(bus) 1494 BF Trip T2 (busbar trip)
BO5 AR CLOSE Cmd. 2851 AR: Close command
Table D-5 Further output relay presettings for 7VK611
Binary Output Allocated Function Indication no. Description
BO1 Relay PICKUP 501 Relay PICKUP
BO2 Relay TRIP 511 Relay GENERAL TRIP command
BO3 Alarm Sum Event 160 Alarm Summary Event
BO4 Not configured 1 No Function configured
BO5 AR CLOSE Cmd. 2851 AR: Close command
BO6 CB Alarm Supp 563 CB alarm suppressed
BO5 AR CLOSE Cmd. 2851 AR: Close command
BO8 BF T2-TRIP(bus) 1494 BF Trip T2 (busbar trip)
BO9 AR 1p Trip Perm 2864 AR: 1pole trip permitted by internal AR
BO10 Relay TRIP 1pL1 512 Relay TRIP command - Only Phase L1
Relay TRIP 3ph. 515 Relay TRIP command Phases L123
BO11 Not configured 1 No Function configured
BO12 Not configured 1 No Function configured
BO13 Relay TRIP 1pL2 513 Relay TRIP command - Only Phase L2
Relay TRIP 3ph. 515 Relay TRIP command Phases L123
BO14 Not configured 1 No Function configured
BO15 Not configured 1 No Function configured
BO16 Not configured 1 No Function configured
BO17 Relay TRIP 1pL3 514 Relay TRIP command - Only Phase L3
Relay TRIP 3ph. 515 Relay TRIP command Phases L123
BO18 Not configured 1 No Function configured
D.3
Default Settings and Protocol-dependent Functions
D.3 Binary output default settings
280 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018