Addr. Parameter Setting Options Default Setting Comments
3470 2.AR: CB? CLOSE YES
NO
NO CB ready interrogation before
reclosing
3471 2.AR SynRequest YES
NO
NO Request for synchro-check after
3pole AR
3472 3.AR: START YES
NO
NO AR start allowed in this cycle
3473 3.AR: T-ACTION 0.01 .. 300.00 sec 0.20 sec Action time
3475 3.AR Tdead 1Flt 0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase faults
3476 3.AR Tdead 2Flt 0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase faults
3477 3.AR Tdead 3Flt 0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase faults
3478 3.AR Tdead1Trip 0.01 .. 1800.00 sec 2147483647 sec Dead time after 1pole trip
3479 3.AR Tdead3Trip 0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3480 3.AR: Tdead EV. 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3481 3.AR: CB? CLOSE YES
NO
NO CB ready interrogation before
reclosing
3482 3.AR SynRequest YES
NO
NO Request for synchro-check after
3pole AR
3483 4.AR: START YES
NO
NO AR start allowed in this cycle
3484 4.AR: T-ACTION 0.01 .. 300.00 sec 0.20 sec Action time
3486 4.AR Tdead 1Flt 0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase faults
3487 4.AR Tdead 2Flt 0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase faults
3488 4.AR Tdead 3Flt 0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase faults
3489 4.AR Tdead1Trip 0.01 .. 1800.00 sec 2147483647 sec Dead time after 1pole trip
3490 4.AR Tdead3Trip 0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3491 4.AR: Tdead EV. 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3492 4.AR: CB? CLOSE YES
NO
NO CB ready interrogation before
reclosing
3493 4.AR SynRequest YES
NO
NO Request for synchro-check after
3pole AR
Information List
No.
Information Type of
Informa-
tion
Comments
2701 >AR on SP >AR: Switch on auto-reclose function
2702 >AR off SP >AR: Switch off auto-reclose function
2703 >AR block SP >AR: Block auto-reclose function
2711 >AR Start SP >External start of internal Auto reclose
2712 >Trip L1 AR SP >AR: External trip L1 for AR start
2713 >Trip L2 AR SP >AR: External trip L2 for AR start
2714 >Trip L3 AR SP >AR: External trip L3 for AR start
2715 >Trip 1pole AR SP >AR: External 1pole trip for AR start
2716 >Trip 3pole AR SP >AR: External 3pole trip for AR start
2727 >AR RemoteClose SP >AR: Remote Close signal
2731 >Sync.release SP >AR: Sync. release from ext. sync.-check
2.2.4
Functions
2.2 Automatic reclosure function (optional)
66 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018