Binary input default settings
Table D-2 Further binary input presettings for 7VK610
Binary Input Allocated Function Indication no. Description
BI1 >AR Start 2711 >External start of internal Auto reclose
>BF release 1432 >BF: External release
BI2 >Trip 3pole AR 2716 >AR: External 3pole trip for AR start
>BF Start 3pole 1415 >BF: External start 3pole
BI3 >CB1 3p Closed 410 >CB1 aux. 3p Closed (for AR, CB-Test)
>CB 3p Closed 379 >CB aux. contact 3pole Closed
BI4 >CB1 Ready 371 >CB1 READY (for AR,CB-Test)
BI5 >Manual Close 356 >Manual close signal
BI6 >FAIL:Feeder VT 361 >Failure: Feeder VT (MCB tripped)
BI7 >FAIL:U4 VT 362 >Failure: Usy4 VT (MCB tripped)
Table D-3 Further binary input presettings for 7VK611
Binary Input Allocated Function Indication no. Description
BI1 >AR Start 2711 >External start of internal Auto reclose
>BF release 1432 >BF: External release
BI2 >BLOCK 1pole AR 2737 >AR: Block 1pole AR-cycle
BI3 >BLOCK 3pole AR 2738 >AR: Block 3pole AR-cycle
BI4 >CB1 Ready 371 >CB1 READY (for AR,CB-Test)
BI5 >Manual Close 356 >Manual close signal
BI6 >FAIL:Feeder VT 361 >Failure: Feeder VT (MCB tripped)
BI7 >FAIL:U4 VT 362 >Failure: Usy4 VT (MCB tripped)
BI8 >Trip L1 AR 2712 >AR: External trip L1 for AR start
>BF Start L1 1435 >BF: External start L1
BI9 >Trip L2 AR 2713 >AR: External trip L2 for AR start
>BF Start L2 1436 >BF: External start L2
BI10 >Trip L3 AR 2714 >AR: External trip L3 for AR start
>BF Start L3 1437 >BF: External start L3
BI11 >CB1 Pole L1 366 >CB1 Pole L1 (for AR,CB-Test)
>CB Aux. L1 351 >Circuit breaker aux. contact: Pole L1
BI12 >CB1 Pole L2 367 >CB1 Pole L2 (for AR,CB-Test)
>CB Aux. L2 352 >Circuit breaker aux. contact: Pole L2
BI13 >CB1 Pole L3 368 >CB1 Pole L3 (for AR,CB-Test)
>CB Aux. L3 353 >Circuit breaker aux. contact: Pole L3
BI14 Not configured 1 No Function configured
BI15 Not configured 1 No Function configured
BI16 Not configured 1 No Function configured
BI17 Not configured 1 No Function configured
BI18 Not configured 1 No Function configured
BI19 Not configured 1 No Function configured
BI20 Not configured 1 No Function configured
D.2
Default Settings and Protocol-dependent Functions
D.2 Binary input default settings
SIPROTEC 4, 7VK61, Manual 279
C53000-G1176-C159-5, Edition 05.2018