C-I/O-11 Input/Output Board(s)
[ein-ausgabebgr-c-io-11-160502-wlk, 1, en_GB]
Figure 3-10
C-I/O-11 input/output board with representation of jumper settings required for checking
configuration settings
Table 3-16 Jumper settings for Pickup Voltages of the binary inputs BI6 and BIG7 on the input/output
board C-I/O-11
Binary Input Jumper Threshold 19 V
1)
Threshold 88V
4)
Threshold 176 V 
5)
BI6 X21 L M H
BI7 X22 L M H
1) 
Factory settings for devices with power supply voltages of DC 24 to 125 V
2) 
Factory settings for devices with power supply voltages of DC 110 to 250 V and
AC 115/230 V
3) 
Only use for control voltages DC 220 to 250 V and AC 230 V
The set nominal current of the current input transformers are checked on the input/output board C-I/O-11. The
jumpers X60 to X63 must be set for one nominal current, i.e. one jumper (X61 to X63) for each input trans-
Mounting and Commissioning
3.1 Mounting and Connections
194 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018