Jumper Nominal current 1 A
Measuring range 100 A
Nominal current 5 A
Measuring range 500 A
X60 1-2 2-3
X61 3-5 4-5
X62 3-5 4-5
X63 3-5 4-5
X64 3-5 4-5
Contacts of relays for binary outputs BO6, BO7 and BO8 can be configured as normally open or normally
closed (see also General Diagrams in the Appendix).
Table 3-13 Jumper setting for the Contact Type of the relays for BO6, BO7 and BO8
For Jumper
Open in quiescent state (NO)
1)
Closed in quiescent state (NC)
BO6 X41 1-2 2-3
BO7 X42 1-2 2-3
BO8 X43 1-2 2-3
1)
delivery condition
The relays for binary outputs BO1 through BO5 can be connected to common potential, or configured individ-
ually for BO1, BO4 and BO5 (BO2 and BO3 are without function in this context) (see also General Diagrams in
the Appendix).
Table 3-14
Jumper settings for the configuration of the Common Potential of BO1 through BO5 or for
configuration of BO1, BO4 and BO5 as Single Relays
Jumper BO1 through BO5 connected to
common potential
1)
BO1, BO4, BO5 configured as single relays (BO2, BO3
without function)
X80 1-2, 3-4 2-3, 4-5
X81 1-2, 3-4 2-3, 4-5
X82 2-3 1-2
1)
delivery condition
Jumpers X71, X72 and X73 serve for setting the bus address. Their position must not be changed. The
following Table lists the jumper presettings.
Table 3-15
Jumper setting of the module addresses of the input/output board C-I/O-2
Jumper Mounting location
X71 1-2 (H)
X72 1-2 (H)
X73 2-3 (L)
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7VK61, Manual 193
C53000-G1176-C159-5, Edition 05.2018