Figure 2-42
Logic diagram of the two-stage breaker failure protection
Circuit breaker not operational
There may be cases when it is already obvious that the circuit breaker associated with a feeder protection relay
cannot clear a fault, e.g. when the tripping voltage or the tripping energy is not available.
In such a case it is not necessary to wait for the response of the feeder circuit breaker. If provision has been
made for the detection of such a condition (e.g. control voltage monitor or air pressure monitor), the monitor
alarm signal can be fed to the binary input
>CB faulty
of the 7VK61. On occurrence of this alarm and a trip
command by the feeder protection, a separate timer T3-BkrDefective is started (see Figure 2-43), which is
normally set to 0. Thus, the adjacent circuit breakers (bus-bar) are tripped immediately in case the feeder
circuit breaker is not operational.