Binary inputs Jumper
Threshold 19 V
1)
Threshold 88 V
4)
Threshold 176 V
5)
BI14 X29 1-2 2-3 3-4
BI15 X30 1-2 2-3 3-4
BI16 X31 1-2 2-3 3-4
BI17 X32 1-2 2-3 3-4
BI18 X33 1-2 2-3 3-4
BI19 X34 1-2 2-3 3-4
BI20 X35 1-2 2-3 3-4
1)
Factory settings for devices with power supply voltages of DC 24 to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 to 250 V and AC 115/230 V
3)
Only use for control voltages DC 220 to 250 V and AC 230 V
Jumpers X71, X72 and X73 on the input/output board C-I/O-4 are used for setting the bus address and must
not be changed. The following Table lists the jumper presettings.
Table 3-9 Jumper setting of the module addresses of the input/output board C-I/O-4
Jumper Mounting location
X71 1-2 (H)
X72 2-3 (L)
X73 1-2 (H)
Input/output module C-I/O-2 up to release7VK61 .../DD
There are two different releases of the input output module C-I/O-2. For devices up to release 7VK61.../DD the
layout of the printed circuit board is shown in Figure 3-8, for devices of release 7VK61.../FF in Figure 3-8.
Mounting and Commissioning
3.1 Mounting and Connections
190 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018