Permissible optical signal attenuation Max. 8 dB, with glass fibre 62.5/125 μm
Transmission distance between two
modules with redundant optical ring
topology and glass fibre 62.5/125 m
2 m with plastic fibre
500 kBit/s max. 1.6 km
1500 kBit/s 530 m
Character idle state (status for “No
character”)
Light OFF
Max. number of modules in optical
rings with 500 kB/s or 1500 kB/s
41
DNP3.0 RS485
Connection for flush-mounted housing rear panel, slot “B”,
9-pole D-subminiature female connector
Connection for surface-mounted
housing
in console housing
Test voltage 500 V; 50 Hz
Transmission rate up to 19200 Baud
Transmission distance max. 1 km
DNP3.0 FO
FO connector type ST connector receiver/transmitter
Connection for flush-mounted housing rear panel, slot “B”
Connection for surface-mounted
housing
in console housing
Transmission rate up to 19200 Baud
Optical wavelength λ = 820 nm
Laser class 1 according to
EN60825-1/-2
Using glass fibre 50/125 μm or
Using glass fibre 62.5/125 μm
Permissible optical signal attenuation max. 8 dB, with glass fibre 62.5/125 μm
Transmission distance max. 1.5 km
Ethernet electrical (EN 100) for IEC 61850 and DIGSI
Connection for flush-mounted housing rear panel, slot “B”
2 x RJ45 female connector
100BaseT acc. to IEEE802.3
Connection for surface-mounted
housing
in console housing
Test voltage (female connector) 500 V; 50 Hz
Transmission rate 100 MBit/s
Transmission distance 20 m
Ethernet optical (EN100) for IEC 61850 and DIGSI
FO connector type ST connector receiver/transmitter
Connection for flush-mounted housing rear panel, slot “B”
Connection for surface-mounted
housing
not available
Transmission rate λ = 1310 nm
Optical wavelength 100 MBit/s
Laser class 1 according to
EN60825-1/-2
Using glass fibre 50 μm/125 μm or Using glass fibre 62,5 μm/125 μm
Permissible optical signal attenuation max. 5 dB, with glass fibre 62,5 μm/125 μm
Transmission distance max. 800 m