EasyManua.ls Logo

Siemens SIPROTEC 4 7VK61 - Page 232

Siemens SIPROTEC 4 7VK61
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrostatic discharge
IEC 60255-22-2, Class IV
and IEC 61000-4-2, Class IV
8 kV contact discharge; 15 kV air discharge, both polarities;
150 pF; R
i
= 330 Ω
Irradiation with HF field, frequency sweep
IEC 60255-22-3, Class III
IEC 61000-4-3, Class III
10 V/m; 80 MHz to 1000 MHz; 80 % AM; 1 kHz
10 V/m; 800 MHz to 960 MHz; 80 % AM; 1 kHz
20 V/m; 1,4 GHz to 2,0 GHz; 80 % AM; 1 kHz
Irradiation with HF field, single frequencies
IEC 60255-22-3, IEC 61000-4-3, Class III
– amplitude-modulated
– pulse-modulated
10 V/m
80 MHz; 160 MHz; 450 MHz; 900 MHz; 80 % AM; 1 kHz; duty
cycle > 10 s
900 MHz; 50 % PM, repetition frequency 200 Hz
Fast transient disturbances
Burst IEC 60255-22-4 and IEC 61000-4-4, Class IV
4 kV; 5 ns/50 ns; 5 kHz; burst length = 15 ms; repetition 300
ms; both polarities; R
i
= 50 Ω; test duration 1 min
High energy surge voltages (SURGE),
IEC 61000-4-5 installation Class 3
- Auxiliary voltage
– Analog measuring inputs, binary inputs, relay outputs
Pulse: 1.2 μs/50 μs
common mode: 2 kV; 12 Ω; 9 µF
diff. mode: 1 kV; 2 Ω; 18 µF
common mode: 2 kV; 42 Ω; 0,5 µF
diff. mode: 1 kV; 42 Ω; 0,5 µF
Line conducted HF, amplitude modulated
IEC 61000-4-6, Class III
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 60255-6
IEC 61000-4-8, Class IV
0,5 mT; 50 Hz,
30 A/m continuous; 300 A/m for 3 s; 50 Hz
Oscillatory Surge Withstand Capability
IEEE Std C37.90.1
2.5 kV (Peak); 1 MHz; τ = 15 μs; 400 Surges per s; test duration
2 s; R
i
= 200 Ω
Fast Transient Surge Withstand Cap.
IEEE Std C37.90.1
4 kV; 5 ns/50 ns; 5 kHz; burst length = 15 ms; repetition rate
300 ms; both polarities; R
i
= 50 Ω; test duration 1 min
Radiated Electromagnetic Interference
IEEE Std C37.90.2
35 V/m; 25 MHz to 1000 MHz
Damped oscillations IEC 60694, IEC 61000-4-12 2.5 kV (peak value), polarity alternating 100 kHz, 1 MHz, 10
MHz and 50 MHz R
i
= 200 Ω
EMC Tests for Interference Emission (Type Test)
Standard:
EN 61000-6-3 (generic standard)
Radio noise voltage to lines, only auxiliary voltage
IECCISPR 22
150 kHz to 30 MHz
Limit class B
Interference field strength
IEC-CISPR 22
30 MHz to 1000 MHz
Limit class B
Harmonic currents on the network lead at AC 230 V
IEC 61000-3-2
Class A limits are observed
Voltage fluctuations and flicker on the network lead at
AC 230 V
IEC 61000-3-3
Limits are observed
Technical Data
4.1 General
232 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018

Table of Contents