EasyManua.ls Logo

Siemens SIPROTEC 4 7VK61 - Page 240

Siemens SIPROTEC 4 7VK61
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pickup value 3Ι
0
>> (earth) for Ι
N
= 1 A
0.05 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for Ι
N
= 5 A
0.25 A to 125.00 A
or ∞ (ineffective)
Delay T
ΙPh
>> (phases) 0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Delay T
3Ι0
>> (earth) 0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Dropout ratio
Approx. 0.95 for Ι/Ι
N
≥ 0.5
Pickup times Approx. 25 ms
Dropout times Approx. 30 ms
Tolerances Currents 3 % of setting value or 1 % nominal current
Times 1 % of setting value or 10 ms
The set times are pure delay times
Overcurrent Stages
Pickup value Ι
Ph
> (phases)
Pickup value Ι
Ph
>>>(phases)
for Ι
N
= 1 A
0.10 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for Ι
N
= 5 A
0.50 A to 125.00 A
or ∞ (ineffective)
Pickup value 3Ι
0
> (earth)
Pickup value 3Ι
0
> (earth)
for Ι
N
= 1 A
0.05 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for Ι
N
= 5 A
0.25 A to 125.00 A
or ∞ (ineffective)
Delay T
ΙPh
> (phases) 0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Delay T
3Ι0
> (earth) 0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Dropout ratio
Approx. 0.95 for Ι/Ι
N
≥ 0.5
Pickup times (fast relays) Approx. 25 ms
Dropout times Approx. 30 ms
Tolerances Currents 3 % of setting value or 1 % nominal current
Times 1 % of setting value or 10 ms
The set times are pure delay times
Inverse Time Stages (IEC)
Pickup value
Ι
Ph
(phases)
for Ι
N
= 1 A
0.10 A to 4.00 A
or ∞ (ineffective)
Increments 0.01 A
for Ι
N
= 5 A
0.50 A to 20.00 A
or ∞ (ineffective)
Pickup value 3Ι
0P
(earth) for Ι
N
= 1 A
0.05 A to 4.00 A
or ∞ (ineffective)
Increments 0.01 A
for Ι
N
= 5 A
0.25 A to 20.00 A
or ∞ (ineffective)
Time multipliers T
ΙP
(phases) 0.05 s to 3.00 s
or ∞ (ineffective)
Increments 0.01 s
T
3Ι0P
(earth) 0.05 s to 3.00 s
or ∞ (ineffective)
Increments 0.01 s
Technical Data
4.3 Overcurrent protection (optional)
240 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018

Table of Contents

Related product manuals