- Ι1 for Ι
N
= 1 A
0.05 A to 2.00 A Increments 0.01 A
for Ι
N
= 5 A
0.25 A to 10.00 A Increments 0.01 A
- U1 2 V to 70 V Increments 1 V
Response Time Approx. 30 ms
Trip Circuit Supervision
Number of monitored circuits 1 to 3
Operation per circuit With 1 binary input or with 2 binary inputs
Pickup and Dropout Time Approx. 1 s to 2 s
Settable delay time for operation with 1 binary input 1 s to 30 s Increments 1 s
Technical Data
4.7 Monitoring Functions
SIPROTEC 4, 7VK61, Manual 249
C53000-G1176-C159-5, Edition 05.2018