Fault Recording
Number of stored fault records Max. 8
Storage time Max. 5 s for each fault
Approx. 15 s in total
Sampling rate at f
N
= 50 Hz 1 ms
Sampling rate at f
N
= 60 Hz 0,83 ms
Switching Statistics
Number of trip events caused by the device Separately for each breaker pole (if single-pole tripping is
possible)
Number of automatic reclosures initiated by the device Separate for 1-pole and 3-pole AR;
Separately for 1st AR cycle
and for all further cyles
Total of interrupted currents Pole segregated
Maximum interrupted current Pole segregated
Real Time Clock and Buffer Battery
Resolution for operational messages 1 ms
Resolution for fault messages 1 ms
Buffer battery Type: 3 V/1 Ah, Type CR 1/2 AA
Self-discharging time approx. 10 years
IEC 61850 GOOSE (inter-device communication)
The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking. The runtime of GOOSE
messages with the protection relay picked up depends on the number of connected IEC 61850 clients. For the devices
applications with protective functions have to be checked in terms of their required runtime. In each case, the manufac-
turer has to be consulted to define the requirements that ensure that the application functions safely.
Technical Data
4.9 Auxiliary Functions
SIPROTEC 4, 7VK61, Manual 255
C53000-G1176-C159-5, Edition 05.2018