Addr. Parameter Function C Setting Options Default Setting Comments
3437 ADT SynRequest Autoreclosure YES
NO
NO Request for synchro-
check after 3pole AR
3438 T U-stable Autoreclosure
Autoreclosure
0.10 .. 30.00 sec 0.10 sec Supervision time for
dead/live voltage
3440 U-live> Autoreclosure
Autoreclosure
30 .. 90 V 48 V Voltage threshold for live
line or bus
3441 U-dead< Autoreclosure
Autoreclosure
2 .. 70 V 30 V Voltage threshold for
dead line
3450 1.AR: START Autoreclosure YES
NO
YES AR start allowed in this
cycle?
3451 1.AR: T-ACTION Autoreclosure 0.01 .. 300.00 sec 0.20 sec Action time
3453 1.AR Tdead 1Flt Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase
faults
3454 1.AR Tdead 2Flt Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase
faults
3455 1.AR Tdead 3Flt Autoreclosure 0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase
faults
3456 1.AR Tdead1Trip Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 1pole trip
3457 1.AR Tdead3Trip Autoreclosure 0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3458 1.AR: Tdead EV. Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving
fault
3459 1.AR: CB? CLOSE Autoreclosure YES
NO
NO CB ready interrogation
before reclosing
3460 1.AR SynRequest Autoreclosure YES
NO
NO Request for synchro-
check after 3pole AR
3461 2.AR: START Autoreclosure YES
NO
NO AR start allowed in this
cycle?
3462 2.AR: T-ACTION Autoreclosure 0.01 .. 300.00 sec 0.20 sec Action time
3464 2.AR Tdead 1Flt Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase
faults
3465 2.AR Tdead 2Flt Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase
faults
3466 2.AR Tdead 3Flt Autoreclosure 0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase
faults
3467 2.AR Tdead1Trip Autoreclosure 0.01 .. 1800.00 sec 2147483647 sec Dead time after 1pole trip
3468 2.AR Tdead3Trip Autoreclosure 0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3469 2.AR: Tdead EV. Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving
fault
3470 2.AR: CB? CLOSE Autoreclosure YES
NO
NO CB ready interrogation
before reclosing
3471 2.AR SynRequest Autoreclosure YES
NO
NO Request for synchro-
check after 3pole AR
3472 3.AR: START Autoreclosure YES
NO
NO AR start allowed in this
cycle?
3473 3.AR: T-ACTION Autoreclosure 0.01 .. 300.00 sec 0.20 sec Action time
3475 3.AR Tdead 1Flt Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase
faults
3476 3.AR Tdead 2Flt Autoreclosure 0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase
faults
Functions, Settings, Information
E.2 Settings
302 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018