No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
127 Auto Reclose ON/OFF (via
system port) (AR ON/OFF)
Device IntS
P
O
N
OF
F
* * LED BO
130 Load angle Phi(PQ Posi-
tive sequence) (φ(PQ Pos.
Seq.))
Meas-
urem.Super
v
OUT * * * LED BO
131 Load angle Phi(PQ)
blocked (φ(PQ Pos) block)
Meas-
urem.Super
v
OUT * * * LED BO
132 Setting error: |PhiA - PhiB|
< 3° (φ Set wrong)
Meas-
urem.Super
v
OUT * * * LED BO
140 Error with a summary
alarm (Error Sum Alarm)
Device OUT O
N
OF
F
* * LED BO 94 47 1 Yes
144 Error 5V (Error 5V) Device OUT O
N
OF
F
* * LED BO 13
5
16
4
1 Yes
160 Alarm Summary Event
(Alarm Sum Event)
Device OUT * * * LED BO 94 46 1 Yes
161 Failure: General Current
Supervision (Fail I
Superv.)
Meas-
urem.Super
v
OUT * * * LED BO 94 32 1 Yes
162 Failure: Current Summa-
tion (Failure Σ I)
Meas-
urem.Super
v
OUT O
N
OF
F
* * LED BO 13
5
18
2
1 Yes
163 Failure: Current Balance
(Fail I balance)
Meas-
urem.Super
v
OUT O
N
OF
F
* * LED BO 13
5
18
3
1 Yes
164 Failure: General Voltage
Supervision (Fail U
Superv.)
Meas-
urem.Super
v
OUT * * * LED BO 94 33 1 Yes
165 Failure: Voltage summa-
tion Phase-Earth (Fail Σ U
Ph-E)
Meas-
urem.Super
v
OUT O
N
OF
F
* * LED BO 13
5
18
4
1 Yes
167 Failure: Voltage Balance
(Fail U balance)
Meas-
urem.Super
v
OUT O
N
OF
F
* * LED BO 13
5
18
6
1 Yes
Functions, Settings, Information
E.3 Information List
314 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018