Loading...
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
10230 U1<(<) Undervolt. is
BLOCKED (U1<(<) BLK)
Voltage
Prot.
OUT O
N
OF
F
ON
OFF
* LED BO 73 30 1 Yes
10231 Over-/Under-Voltage
protection is ACTIVE
(U</> ACTIVE)
Voltage
Prot.
OUT O
N
OF
F
* * LED BO 73 31 1 Yes
10240 Uph-e> Pickup (Uph-e>
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 40 2 Yes
10241 Uph-e>> Pickup (Uph-e>>
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 41 2 Yes
10242 Uph-e>(>) Pickup L1
(Uph-e>(>) PU L1)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 42 2 Yes
10243 Uph-e>(>) Pickup L2
(Uph-e>(>) PU L2)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 43 2 Yes
10244 Uph-e>(>) Pickup L3
(Uph-e>(>) PU L3)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 44 2 Yes
10245 Uph-e> TimeOut (Uph-e>
TimeOut)
Voltage
Prot.
OUT * * * LED BO
10246 Uph-e>> TimeOut (Uph-
e>> TimeOut)
Voltage
Prot.
OUT * * * LED BO
10247 Uph-e>(>) TRIP command
(Uph-e>(>) TRIP)
Voltage
Prot.
OUT * ON * LED BO 73 47 2 Yes
10248 Uph-e> Pickup L1 (Uph-e>
PU L1)
Voltage
Prot.
OUT * * * LED BO
10249 Uph-e> Pickup L2 (Uph-e>
PU L2)
Voltage
Prot.
OUT * * * LED BO
10250 Uph-e> Pickup L3 (Uph-e>
PU L3)
Voltage
Prot.
OUT * * * LED BO
10251 Uph-e>> Pickup L1 (Uph-
e>> PU L1)
Voltage
Prot.
OUT * * * LED BO
10252 Uph-e>> Pickup L2 (Uph-
e>> PU L2)
Voltage
Prot.
OUT * * * LED BO
10253 Uph-e>> Pickup L3 (Uph-
e>> PU L3)
Voltage
Prot.
OUT * * * LED BO
10255 Uph-ph> Pickup (Uphph>
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 55 2 Yes
10256 Uph-ph>> Pickup
(Uphph>> Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 56 2 Yes
10257 Uph-ph>(>) Pickup L1-L2
(Uphph>(>)PU L12)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 57 2 Yes
Functions, Settings, Information
E.3 Information List
SIPROTEC 4, 7VK61, Manual 337
C53000-G1176-C159-5, Edition 05.2018

Table of Contents

Related product manuals