No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
10290 U2> Pickup (U2> Pickup) Voltage
Prot.
OUT * ON
OFF
* LED BO 73 90 2 Yes
10291 U2>> Pickup (U2>>
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 91 2 Yes
10292 U2> TimeOut (U2>
TimeOut)
Voltage
Prot.
OUT * * * LED BO
10293 U2>> TimeOut (U2>>
TimeOut)
Voltage
Prot.
OUT * * * LED BO
10294 U2>(>) TRIP command
(U2>(>) TRIP)
Voltage
Prot.
OUT * ON * LED BO 73 94 2 Yes
10300 U1< Pickup (U1< Pickup) Voltage
Prot.
OUT * ON
OFF
* LED BO 73 10
0
2 Yes
10301 U1<< Pickup (U1<<
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 10
1
2 Yes
10302 U1< TimeOut (U1<
TimeOut)
Voltage
Prot.
OUT * * * LED BO
10303 U1<< TimeOut (U1<<
TimeOut)
Voltage
Prot.
OUT * * * LED BO
10304 U1<(<) TRIP command
(U1<(<) TRIP)
Voltage
Prot.
OUT * ON * LED BO 73 10
4
2 Yes
10310 Uph-e< Pickup (Uph-e<
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 11
0
2 Yes
10311 Uph-e<< Pickup (Uph-e<<
Pickup)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 11
1
2 Yes
10312 Uph-e<(<) Pickup L1
(Uph-e<(<) PU L1)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 11
2
2 Yes
10313 Uph-e<(<) Pickup L2
(Uph-e<(<) PU L2)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 11
3
2 Yes
10314 Uph-e<(<) Pickup L3
(Uph-e<(<) PU L3)
Voltage
Prot.
OUT * ON
OFF
* LED BO 73 11
4
2 Yes
10315 Uph-e< TimeOut (Uph-e<
TimeOut)
Voltage
Prot.
OUT * * * LED BO
10316 Uph-e<< TimeOut (Uph-
e<< TimeOut)
Voltage
Prot.
OUT * * * LED BO
10317 Uph-e<(<) TRIP command
(Uph-e<(<) TRIP)
Voltage
Prot.
OUT * ON * LED BO 73 11
7
2 Yes
10318 Uph-e< Pickup L1 (Uph-e<
PU L1)
Voltage
Prot.
OUT * * * LED BO
10319 Uph-e< Pickup L2 (Uph-e<
PU L2)
Voltage
Prot.
OUT * * * LED BO
10320 Uph-e< Pickup L3 (Uph-e<
PU L3)
Voltage
Prot.
OUT * * * LED BO
Functions, Settings, Information
E.3 Information List