Figure 2-10 Connection example with external protection device for 1-/3-pole reclosure; AR control mode =
with TRIP
[anschlussbsp-ext-schutzger-3-pol-we-wlk-310702, 1, en_GB]
Figure 2-11 Connection example with external protection device for 3-pole reclosure; AR control mode =
with TRIP
But if the internal automatic reclose function is controlled by the pickup (only possible for 3-pole tripping: 110
Trip mode = 3pole only), the phase-selective
pickup signals of the external protection must be connected
if distinction shall be made between different types of fault. The general trip command then suffices for trip-
ping (No. 2746). Figure 2-12 shows a connection example.
Functions
2.2 Automatic reclosure function (optional)