Configuration
5-61
7SA6 Manual
C53000-G1176-C156-2
Operating Messag-
es from the Timing
System
After the Time interruption ON message, the you must take into account that
the clock will jump. This message is issued under the following circumstances:
if a synchronization interruption lasts longer than the tolerance time interval men-
tioned above, or as mentioned above, if the synchronization mode is changed;
if a time jump is anticipated. The message itself is stamped with the old time.
The message Time interruption OFF is triggered:
when the synchronization is re-established (e.g., after a break in reception by the
radio clock);
immediately after a time jump. This message is stamped with the new time after the
jump, thus allowing determination of the jump interval.
Time Format The time display may be set using either the European format (DD.MM.YYYY) or the
US format (MM/DD/YYYY).