EasyManuals Logo

Siemens siprotec 7SA6 User Manual

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #239 background imageLoading...
Page #239 background image
Functions
6-497SA6 Manual
C53000-G1176-C156-2
Figure 6-28 Circuit breaker closure onto a fault
6.2.3.2 Applying the Function Parameter Settings
General Function
Parameters
The distance protection can be switched on or off with the parameter in address 1201
FCT Distance ON/OFF
The minimum current for fault detection Minimum Iph> (address 1202)issetsome-
what (approx. 10 %) below the minimum short-circuit current that may occur.
The setting parameters for the treatment of earth faults
1203 3I0> Threshold and
1204 3U0> Threshold were already discussed in Sub-section 6.2.1.2.
Correction of
Measured Values
on Parallel Lines
(optional)
The mutual coupling between the two lines of a double-circuit configuration is only rel-
evant to the 7SA6 when it is applied on a double-circuit line and when it is intended to
implement parallel line compensation. A prerequisite is that the earth current of the
parallel line is connected to the I
4
measuring input of the 7SA6 and this is entered in
the configuration settings.
In this case, the setting
Paral.Line Comp = YES must be set in address 1215;oth-
erwise the presetting
NO remains.
The coupling factors were already set as part of the general protection data (Sub-sec-
tion 6.1.3), as was the reach of the parallel line compensation.
DoubleEarthFaults
in Earthed Systems
The loop selection for double earth faults is set in address 1221A 2Ph-E faults
(Phase–Phase–Earth–fault detection). This setting can only be modified with DIGSI
®
4under“Additional Settings”. In general the Block leading Ø (blocking of the
leading phase, presetting) is favourable, because the leading phase-earth loop tends
to overreach, especially in conjunction with large earth fault resistance. In certain cas-
es (fault resistance phase-phase larger than phase-earth) the setting
Block lag-
ging
Ø (blocking of the lagging phase) may be more favourable. The selection of all
affected loops with the setting
All loops allows a maximum degree of redundancy.
Alternatively,
Ø-Ø loops only may be evaluated. This ensures the most accuracy
for two phase to earth faults. Ultimately it is possible to declare the
Ø-E loops only as valid.
DoubleEarthFaults
in Non-earthed Sys-
tems
In isolated or resonant-earthed systems it must be guaranteed that the preference for
double earth faults in whole galvanically-connected systems is consistent. The double
earth fault preference is set in address
1220 PHASE PREF.2phe.
Z1B instantaneous.
SOTF zone
Zone Z1B
Inactive
PICKUP
„1“
SOTF Op. mode
1
&
1
&
Z2 instantaneous.
Z3 instantaneous.
Z4 instantaneous.
Z5 instantaneous.
ENABLE Z1B
3611
1232

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals