6-717SA6 Manual
C53000-G1176-C156-2
6.2.5.2 Applying the Function Parameter Settings
The trip delay times of the distance stages and intervention options which are also
processed in the tripping logic of the distance protection were already considered with
the zone settings (Sub-sections 6.2.4.2).
The parameter in address
1232 SOTF zone which determines the response during
switching onto a short-circuit was already set as part of the general data of the dis-
tance protection (Sub-section 6.2.3.2).
Further setting options which affect the tripping are described as part of the tripping
logic of the device (refer to Sub-section 6.22.4).