Functions
6-312 7SA6 Manual
C53000-G1176-C156-2
In the event of transfer to a central device, the request for data transfer can be exe-
cutedautomaticallyandcanbeselectedtotakeplaceaftereachfaultdetectionbythe
protection, or only after a trip.
6.23.4 Applying the Function Parameter Settings
Minimum,
Maximum and
Average Values
In addresses 2811 to 2814 you can determine the time intervals for the calculation
of minimum, maximum and average values.
The tracking of minimum and maximum values can be reset automatically at a pre-
definied point in time. To select this feature, address
2811 MinMax cycRESET is set
to
Yes. The point in time when reset is to take place (the minute of the day in which
reset will take place) is set in address
2812 MiMa RESET TIME.Theresetcycle(in
days) is entered at address
2813 MiMa RESETCYCLE, and the date for starting the
cyclical process in days after completion of the configuration procedure is entered in
address
2814 MinMaxRES.START.
The time interval for measured value averaging is set at address
2801 DMD
Interval
. The first number specifies the averaging time window in minutes while the
second number determines the number of updates within the time window. A setting
of
15 Min., 3 Subs, for example, means that time averaging occurs for all
measured values that arrive within 15 minutes, and that output is updated three times
during the 15 minute window, or every 15/3 = 5 minutes.
Determine in address
2802 DMD Sync.Time whether the selected time period for the
averaging is to begin on the hour (
On The Hour) or if it is to be synchronized with a
different point in time (
15 After Hour, 30 After Hour or 45 After Hour).
If the settings for averaging are changed, then the measured values stored in the
buffer are deleted, and new results for the average calculation are only available after
the set time period has passed.
Set Points The settings are entered under Measurement (Measurement) in the sub-menu
SET POINTS (MV) by overwriting the existing values.
Data Storage for
Fault Recording
The configuration of the fault recording memory is done in the sub-menu Fault re-
cording
of the menu PARAMETER. A distinction is made between the reference in-
stant (relative time = 0) and the storage criterion (trigger ) of the fault recording (ad-
dress
402A WAVEFORMTRIGGER). This setting can only be modified with DIGSI
®
4un-
der
Additional Settings”. Normally the reference instant is the occurrence of device
fault detection, i.e. the fault detection of any protection function is allocated with the
timestamp0.Thefaultdetectioncanalsobethestoragecriterion(
Save w. Pickup)
orthedevicetripcommand(
Save w. TRIP) can be the storage criterion. The device
tripcommandcanalsobeusedasreferencetime(
Start w. TRIP); in this case it
is also the storage criterion.
A fault event starts with the fault detection of any protection function and ends with the
resetofthelastfaultdetection.Usuallythisisalsotheextentofafaultrecording(ad-
dress
403A WAVEFORM DATA = Fault event). If automatic reclosure is implement-
ed, the entire system disturbance possibly with several reclose attempts up to
the ultimate fault clearance can be stored (address
403A WAVEFORM DATA = Power
System fault
). This facilitates the representation of the entire system fault history,

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals