Appendix
A-757SA6 Manual
C53000-G1176-C156-2
A.5 Protocol Dependent Functions
Protocol → IEC 60870–5–103
Profibus FMS Profibus DP DNP3.0 Additional
Service
Interface
(optional)
Function ↓
Operational Measured
Values
Yes Yes Yes Yes Yes
Metering Values Yes Yes Yes Yes Yes
Fault Recording Yes Yes No. Only via Additio-
nal Service Interface
No. Only via Additio-
nal Service Interface
Yes
Protective Setting from
Remote
No. Only via Additional
Service Interface
Yes No. Only via Additio-
nal Service Interface
No. Only via Additio-
nal Service Interface
Yes
User-defined Alarms and
Switching Objects
Yes Yes Pre-defined
“User defined
Annunciations”
in CFC
Pre-defined
“User defined
Annunciations”
in CFC
Yes
Time Sychronism Via Protocol;
DCF77/IRIG B;
Interface;
Binary Input
Via Protocol;
DCF77/IRIG B;
Interface;
Binary Input
Via DCF77/IRIG B;
Interface;
Binary Input
Via DCF77/IRIG B;
Interface;
Binary Input
–
Alarms with Time Stamp Yes Yes No Yes Yes
Commissioning Tools:
• Alarm and Measured
Value Transmission
Blocking
Yes Yes No No Yes
• Generate Test Alarms
Yes Yes No No Yes
Physical Mode Asynchronous Asynchronous Asynchronous Asynchronous –
Transmission Mode Cyclic/Event Cyclic/Event Cyclic Cyclic/Event –
Baudrate 4800 to 38400 Up to 1.5 MBaud Up to 1.5 MBaud 2400 to 19200 2400 to
115200
Type RS232
RS485
Optical Fibres
RS485
Optical Fibres
• Single Ring
• Double Ring
RS485
Optical Fibres
• Double Ring
RS485
Optical Fibres
RS232
RS485
Optical
Fibres