Functions
6-1097SA6 Manual
C53000-G1176-C156-2
As soon as the Distance Protection has detected a fault in reverse direction, the block-
ing signal is sent (e.g.
Dis.T.SEND”, FNo 4056).Thesendsignalcanbeprolonged
in address
2103A. If the fault is in forward direction, the blocking signal is stopped (e.g.
Dis.T.BL STOP“, FNo 4070). To achieve a very fast-reacting blocking scheme in-
clude the output signal of the jump detector for the send signal. Therefore allocate the
output
DisJumpBlocking”(FNo4060) also to the output relay to the signal trans-
mitting equipment during configuration. Since this jump signal usually appears when
a measured value suddenly changes, the latter should only be applied, if guaranteed
that the transmission channel has a fast response to the reset of the send signal.
If there is a disturbance in the signal transmission path the overreaching zone can be
blocked via a binary input. The distance protection operates with the usual time grad-
ingcharacteristic(nondelayedtripinZ1).TheoverreachingzoneZ1Bcanthenbeac-
tivatedbyanautomaticreclosefunctionviathebinaryinput“
>Enable ARzones”and
address
1357 1st AR -> Z1B setto“Yes”(referalsotoFigure6-38bottom).
The influence of signals resulting from transients during clearance of external faults or
from direction reversal during the clearance of faults on parallel lines, is neutralized by
the “Transient Blocking”. It prolongs the blocking signal by the transient blocking time
TrBlk BlockTime (address 2110), if it has been present for the minimum duration
equal to the waiting time
TrBlk Wait Time (address 2109).
It lies in the nature of the blocking scheme that single end fed short circuits can also
be tripped rapidly without any special measures, as the non feeding end cannot gen-
erate a blocking signal.
6.6.1.8 Pilot Wire Comparison
The following scheme is suited for conventional transmission media.
In the pilot wire comparison the overreaching zone Z1B functions as instantaneous
zone at both ends of the protected line. Zone Z1B is set to reach beyond the next sta-
tion. The pilot wire comparison avoids non-selective tripping.
The information exchange between both line ends is carried out via a closed quiescent
current loop (Figure 6-64) that is fed by a substation battery. One NC contact must be
allocated for each signal output, the receiving input must be configured to low-active”.
Alternatively two auxiliary relay combinations (e.g. 7PA5210–2A) can be used for in-
verting the contact.
In the quiescent state the pilot wires carry direct current that, at the same time, moni-
tors the healthy state of the connection.
If the Distance Protection picks up, the following signal appears:
Dis.T.SEND”. The
NC contact is opened and the pilot wire loop is initially interrupted. A trip by Z1B is
blocked via the receiving input
>DisTel Rec.Ch1“. If the protection system then de-
tects a fault within the overreaching zone Z1B, the send signal resets. The NC contact
returns to its quiescent state (closed). If the loop in the remote station is also closed
after the same sequence, the loop is energized again: the tripping is again released at
both ends.
In case the short-circuit occurred outside the protected line the pilot wire loop is also
interrupted by the pickup of both devices (both NC contacts Dis.T.SEND” are
opened). Since the send signal will not reset at least one of the line ends (fault is not
inlinedirectioninzoneZ1B),theloopatthatendwillremainopen.Bothreceivingin-
puts are deenergized and block the tripping (because of “L-active”). The other dis-

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals