Functions
6-1577SA6 Manual
C53000-G1176-C156-2
Figure 6-89 Logic diagram of the weak infeed tripping
*)
*)
>Dis.T.RecCh1L1
4207
U
L1
Two terminals
Three terminals
3202
Line Config.
&
„1“
Two terminals
Three terminals
2102
Line Config.
„1“
1
EF OFF/BLOCK
5040
ms
&
S
R
Q
I
E
3I
0
3105 3IoMin Teleprot
EF Pickup
1
&
2501
FCT Weak Infeed
ECHO only
OFF
ECHO and TRIP
„1“
U
L1
2505
UNDERVOLT.
VT loss
&
Dist. OFF/BLOCK
40
ms
&
S
R
Q
&
PICKUP L1
CB closed L1
&
1
&
W/I Pickup L1
>BLOCK Weak Inf
&
U
L2
U
L2
2505 UNDERVOLT.
&
S
R
Q
&
PICKUP L2
CB closed L2
&
1
&
U
L3
U
L3
2505
UNDERVOLT.
&
S
R
Q
&
PICKUP L3
CB closed L3
&
1
&
with earth fault protection
with dist. protection
*)
*)
*)
*)
applies to PUTT and
POTT;
with unblockschemes,
the ”unblock” signals
apply acc. to Fig. 6-61
*)
*)
*)
applies to direc. comp;
with unblock schemes the
“unblock signals apply
4203
>Dis.T.RecCh1L2
4208
>Dis.T.RecCh1L3
4209
>Dis.Tel Rec.Ch1
4206
>Dis.Tel Rec.Ch2
4210
>EF Rec.Ch1
1318
>EF Rec.Ch2
1319
4232
W/I Pickup L24233
W/I Pickup L3
4234
Undervoltage
2502 Trip/Echo DELAY
2503
Trip EXTENSION
2502
2502
Trip/Echo DELAY
50

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals