EasyManua.ls Logo

Siemens siprotec 7SA6 - Page 362

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-172 7SA6 Manual
C53000-G1176-C156-2
line onto a fault usually causes a large fault current. It is important to avoid that the
selected stage picks up in a transient way when energizing the line.
Inverse Time
Overcurrent Stages
IP, 3I0P
with IEC
In the case of the inverse time overcurrent stages, various characteristics can be se-
lected, depending on the version of the device and the configuration (Section 5.1, ad-
dress
126). For the IEC–curves (address 126 Back-Up O/C = TOC IEC)thefollow-
ingareavailableinaddress
2660 IEC Curve:
Inverse (normal inverse, Type A according to IEC 60255–3),
Very inverse (very inverse, Type B according to IEC 60255–3),
Extremely inverse (extremely inverse, Type C according to IEC 60255–3), and
LongTimeInverse (longtime, Type B according to IEC 60255–3).
The curves and equations that the curves are based on, are shown in the technical
data (Section 10.5, Figure 10-1).
For the setting of the current thresholds
Ip> (address 2640)and3I0p PICKUP (ad-
dress
2650) the same considerations as for the overcurrent stages of the definite time
protection (see above) apply. In this case it must be noted that a safety margin be-
tween the pick-up threshold and the set value has already been incorporated. Pick-up
only occurs at a current which is approximately 10 % above the set value.
The above example shows that the maximum expected operating current may directly
be applied as setting here:
primary: Set value Ip> = 630 A,
secondary: SetvalueIp>=5.25A,i.e.(630A/600A)·5A.
The time multiplier setting
T Ip Time Dial (address 2642) is derived from the grad-
ing plan applicable to the network. If implemented as emergency overcurrent protec-
tion, shorter tripping times are advisable (one grading time margin above the fast trip-
ping stage), as this function is only activated in the case of the loss of the
local meas-
ured voltage.
The time multiplier setting
T 3I0p TimeDial (address 2652) can usually be set
smaller according to a separate earth fault grading plan.
In addition to the current dependant time delay an additional constant time length de-
lay can be set if required. The setting
T Ip Add (address 2646 for phase currents)
and
T 3I0p Add (address 2656 forearthcurrents)areinadditiontothetimedelays
resulting from the set curves.
The setting parameter
I(3I0)p Tele/BI (address 2670) determines if it is possible
to use the binary input
>O/C InstTRIP”(F.No.7110) to bypass the trip delays T
Ip Time Dial
(address 2642) including the additional time T Ip Add (address
2646)andT 3I0p TimeDial (address 2652) including the additional time T 3I0p
Add
(address 2656). The binary input (if it is assigned) is common to all stages of the
overcurrent protection. With the setting
I(3I0)p Tele/BI = Yes it is therefore de-
termined that the I
P
–stage trips without delay following pick-up if an operate signal is
present at the binary input; with the setting
I(3I0)p Tele/BI = No the set time de-
lays always come into effect.
IftheIp-stageistotripwhenswitchingthelineontoafaultwithoutorwithashortde-
lay,
SOTF Time DELAY (address 2680, see above and refer to Sub-section “Gener-
al”), the parameter
I(3I0)p SOTF (address 2671)issettoYes. We recommend,
however, not to choose the sensitive stage for the switch on to fault function as ener-
gizing of the line on to a fault should cause a large fault current. It is important to avoid
that the selected stage picks up in a transient way during line energization.

Table of Contents

Other manuals for Siemens siprotec 7SA6

Related product manuals