Functions
6-2097SA6 Manual
C53000-G1176-C156-2
If there is a risk of stability problems in the network during a three-pole interruption,
the setting in address
3437 ADT SynRequest should be Yes.Inthiscasethevoltage
of the line and busbar are checked after a three pole trip and before reclosure to de-
termine if sufficient synchronism exists. This assumes that the device has a voltage
and synchronism check capability or that an external device is available for this pur-
pose. If only single-pole reclosure cycles are executed or no stability problems are ex-
pected during three-pole dead times (e.g. due to close meshing of the network or in
radial networks), set address
3437 to No.
Addresses
3438 and 3440 are only significant if the voltage-controlled adaptive dead
time is used. Set under address
3440 U-live> the limit voltage phase–earth above
which the line is considered to be fault-free. The setting must be smalIer than the low-
est expected operating voltage. The setting is applied in Volts secondary. This value
can be entered as a primary value when parametrizing with a PC and DIGSI
®
4. Ad-
dress
3438 T U-stable determines the measuring time used to determine that the
line is fault free with this return voltage. It should be longer than any transient oscilla-
tions resulting from line energization.
1st Reclosure Cy-
cle
If working on a line with adaptive dead time, no further parameters are needed for the
individual reclose cycles here. All the following parameters assigned to the individual
cycles are then superfluous and inaccessible.
Address
3450 1.AR: START is only available if the automatic reclosure is configured
with action time in the operating mode, i. e. if address
134 AR control mode =
Pickup w/ Tact
or Trip w/ Tact was set when configuring the protection func-
tions (the first setting only applies to three-pole tripping). It determines whether auto-
matic reclosure should be started at all with the first cycle. This address is included
mainly for the sake of uniformity of the parameters for all the reclosure cycles and must
be set to
Yes for the first cycle. If several cycles are used it is possible to control (in
control mode
with PICKUP) the effect of the individual cycles with this parameter and
various action times. Notes and examples can be found in section 6.14.1 under subti-
tle “Action Times” (page 190).
The action time
1.AR: T-ACTION (address) is the time after pickup (fault detection)
by any protective function which can start the automatic reclosure function within
which the trip command must appear. If the command does not appear until after the
action time has expired, there is no reclosure. Depending on the configuration of the
protective functions (see section 5.1) the action time may also be omitted; this applies
especially when an initiating protective function has no fault detection signal.
Depending on the configured operating mode of the automatic reclosure (see section
5.1 under address
134 AR control mode) only addresses 3456 and 3457 (if con-
trol mode
with TRIP)ortheaddresses3453 to 3455 (if operating mode with PICK-
UP
) are available.
In the control mode
with TRIP it is possible to set different dead times for single-pole
and three-pole reclose cycles. Whether single-pole or three-pole tripping takes place
depends solely on the initiating protection functions. Single-pole tripping is only possi-
ble of course if the device and the corresponding protection function are also capable
of single-pole tripping.
Address
3456 1.AR Tdead1Trip isthedeadtimeafter1-poletripping,
Address
3457 1.AR Tdead3Trip isthedeadtimeafter3-poletripping.
If only single-pole reclose cycle are to be allowed, the dead time for three-pole tripping
must be set to
. If only three-pole reclose cycle are to be allowed, the dead time for
single-pole tripping must be set to
; the protection then trips three-pole for all fault
types.

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals