EasyManuals Logo

Siemens siprotec 7SA6 User Manual

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #465 background imageLoading...
Page #465 background image
Functions
6-2757SA6 Manual
C53000-G1176-C156-2
Sampling
Frequency
The sampling frequency and the synchronism of the internal buffer modules is contin-
uously monitored. If deviations occur which cannot be removed by re-synchronization,
the processor system is rebooted.
Measured Value
Acquisition
Currents
Four measuring inputs are available in the current circuits. If the three phase currents
and the earth current from the current transformer star-point or from a separate earth
current transformer on the protected circuit are connected to the device, the sum of
the four digitized currents must equal 0. Faults in the current circuits are detected if
I
F
=|I
L1
+ I
L2
+ I
L3
+k
I
· I
E
|>ΣI THRESHOLD · I
N
+ ΣI FACTOR · I
max
whereby k
I
(parameter I4/Iph CT) takes the eventual ratio difference of a separate
I
E
–current transformer into consideration (e.g. core balance CT). ΣI THRESHOLD and
ΣI FACTOR are setting parameters. The amount ΣI FACTOR · I
max
takes the permis-
sible current proportional ratio errors of the input transducers into account which are
particularly prevalent during large fault currents (Figure 6-139). The reset ratio is ap-
prox. 97 %.
This failure is alarmed by
Failure Σ I”.
Figure 6-139 current sum monitoring
Measured Value
Acquisition
Voltages
Four measuring inputs are available in the voltage circuits: three for phase–earth volt-
ages as well as one input for the displacement voltage (e-n voltage of an open delta
connection) or a busbar voltage. If the displacement voltage is connected to the de-
vice, the sum of the three digitized phase voltages must equal three times the zero se-
quence voltage. Errors in the voltage transformer circuits are detected when
U
F
=|U
L1
+U
L2
+U
L3
+k
U
·U
EN
|>25V.
The factor k
U
allows for a difference of the transformation ratio between the displace-
ment voltage input and the phase voltage inputs (parameter
Uph / Udelta). The
reset ratio is approx. 97 %.
This fault is alarmed by
Fail Σ U Ph-E”.
Note:
The current sum monitoring is only effective if the fourth current measuring input (I
4
)
is connected to measure the earth current of the protected line.
I
F
I
N
I
max
I
N
ΣI THRESHOLD
slope:
ΣI FACTOR

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals