EasyManuals Logo

Siemens siprotec 7SA6 User Manual

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #467 background imageLoading...
Page #467 background image
Functions
6-2777SA6 Manual
C53000-G1176-C156-2
Figure 6-140 Current symmetry monitoring
Broken Conductor A broken conductor of the protected line or in the current transformer secondary circuit
canbedetected,iftheminimumcurrent
BALANCE I LIMIT flowsviathefeeder.Ifa
current symmetry failure is detected and the minimum current is below the threshold
PoleOpenCurrent (address 1130, refer to subsection 6.1.3), an interruption of this
conductor may be assumed. After approximately 5 s the device issues the alarm
Fail Conductor”.
Voltage Symmetry During normal system operation, a certain degree of voltage symmetry can be as-
sumed. The symmetry is monitored in the device with a magnitude comparison. The
smallest phase voltage is compared to the largest. Non-symmetry is detected when
|U
min
|/|U
max
|<BAL. FACTOR U
as long as |U
max
|>BALANCE U-LIMIT
U
max
is the largest and U
min
is the smallest of the three voltages. The symmetry factor
BAL. FACTOR U provides a measure of the voltage unsymmetry, the threshold value
BALANCE U-LIMIT defines the lower limit of the operating range for this monitoring
function (refer to Figure 6-141). Both parameters can be set. The reset ratio is approx.
97 %.
This failure is alarmed by
Fail U balance”.
Figure 6-141 Voltage symmetry monitoring
I
min
I
N
slope:
I
max
I
N
BALANCE I LIMIT
BAL. FACTOR I
U
min
V
BALANCE U-LIMIT
slope:
BAL. FACTOR U
U
max
V

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals