EasyManua.ls Logo

Siemens siprotec 7SA6 - Page 569

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control During Operation
7-557SA6 Manual
C53000-G1176-C156-2
7.4.5 Tagging
To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in inter-
locking checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
From PC with
DIGSI
®
4
With a device ready for operation, first press the key. The MAIN MENU appears.
Using the key, select the menu item
Control and move to editing the control func-
tions with the key. The selection
CONTROL appears.
Select the item
Tagging with the key and switch to the next selection using the
key. The selection
TAGGING appears. See Figure 7-56. The status of the tagging
is displayed
Tagging Display, or changed using Tagging Set.
Figure 7-56 Tagging Equipment from the HMI
:
MENU
TAGGING 01/02
---------------------
Display –> 1
Set –> 2
CONTROL 02/03
---------------------
Breaker/Switch –> 1
Tagging –> 2
Interlock –> 3
MAIN MENU 03/05
--------------------
Annunciation –> 1
Measurement –> 2
Control –> 3
Note:
The Manual Overwrite function is always done using the HMI on the SIPROTEC
®
4
devices.

Table of Contents

Other manuals for Siemens siprotec 7SA6

Related product manuals