Technical Data
10-177SA6 Manual
C53000-G1176-C156
Measuring tolerances
with sinusoidal quantities
and U
K
/U
N
>
0.1
1
) Secondary values based on I
N
=1A;forI
N
=5Atheymustbemultipliedwith5.
2
) Secondary values based on I
N
=1A;
for I
N
= 5 A the impedances must be devided by 5.
Times Shortest trip time approx. 17 ms (50 Hz) / 15 ms (60 Hz)
with fast relays
approx. 12 ms (50 Hz) / 10 ms (60 Hz)
with high–speed relays
Drop-off time approx. 30 ms
Stage timers 0.00 s to 30.00 s;
(steps 0.01 s)
for all zones;
separate time setting possibilities for
single-phase and multi-phase faults
for the zones Z1, Z2, and Z1B
Time expiry tolerances 1 % of set value or 10 ms
The set times are pure delay times.
Emergency
Operation
In case of measured voltage failure, See Section 10.10
e.g. voltage secondary mcb trip
X
X
--------
5% for30° ϕ
sc
90°≤≤
R
R
--------
5% for0° ϕ
sc
60°≤≤
Z
Z
-------
5% for–30° ϕ
sc
ϕ
line
30°≤≤

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals