EasyManua.ls Logo

Siemens siprotec 7SA6 - Page 688

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
10-20 7SA6 Manual
C53000-G1176-C156
Tolerances current 3 % of set value or 1% of nominal current
time 1 % of set value or 10 ms
The set times are pure delay times.
1) Secondary values based on I
N
=1A;forI
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(definite time)
Pickup value 3I
0
> 0.05 A to 25.00 A
1
) (steps 0.01 A)
or 0.003 A to 25.000 A
1
) (steps 0.001 A)
Delay time T
3I0>
0.00 s to 30.00 s (steps 0.01 s)
or
(ineffective)
Drop-off to pick-up ratio approx. 0.95 for I/I
N
0.5
Pickup time (for 1.5* Setting Value) approx. 45 ms
(for
2 * Setting Value) approx. 35 ms
Drop-off time approx. 30 ms
Tolerances current 3 % of set value or 1% of nominal current
time 1 % of set value or 10 ms
The set times are pure delay times.
1) Secondary values based on I
N
=1A;forI
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(inverse time acc.
IEC)
Pickup value 3I
0P
0.05 A to 25.00 A
1
) (steps 0.01 A)
or 0.003 A to 25.000 A
1
) (steps 0.001 A)
Time factor T
3I0P
0.05 s to 3.00 s (steps 0.01 s)
or
(ineffective)
Additional time delay T
3I0Pverz
0.00 s to 30.00 s (steps 0.01 s)
or
(ineffective)
Characteristics see Figure 10-1
Tolerances current pickup at 1.05
I/3I
0P
1.15
times 5 % ± 15 ms for 2
I/3I
0P
20
and T
3I0P
/s 1
1) Secondary values based on I
N
=1A;forI
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(inverse time acc.
ANSI)
Pickup value 3I
0P
0.05 A to 25.00 A
1
) (steps 0.01 A)
or 0.003 A to 25.000 A
1
) (steps 0.001 A)
Time factor D
3I0P
0.50 s to 15.00 s (steps 0.01 s)
or
(ineffective)
Additional time delay T
3I0Pverz
0.00 s to 30.00 s (steps 0.01 s)
or
(ineffective)
Characteristics see Figures 10-2 and 10-3
Tolerances current pickup at 1.05
I/3I
0P
1.15
times 5 % ± 15 ms for 2
I/3I
0P
20
and D
3I0P
/s 1
1) Secondary values based on I
N
=1A;forI
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(logarithmic in-
verse)
Pickup value 3I
0P
0.05 A to 25.00 A
1
) (steps 0.01 A)
or 0.003 A to 25.000 A
1
) (steps 0.001 A)
Startstromfaktor 3
I0P FAKTOR
1.0 to 4.0 (steps 0.1)

Table of Contents

Other manuals for Siemens siprotec 7SA6

Related product manuals