Appendix
A-697SA6 Manual
C53000-G1176-C156-2
Table A-8 Further binary output presettings 7SA6*1–*A/E/J, 7SA6*2–*A/E/J/B/F/K and
7SA613–*A
Binary
Output
LCD Text Function
No.
Remarks
BO2 Relay TRIP 511 Device (general) trip command
2
)
BO10 Dis.T.SEND 4056 Distance protection teleprotection send
signal
BO12 AR CLOSE Cmd. 2851
3
) Automatic reclosure close command
3
)
BO14 Relay TRIP 511
2
) Device (general) trip command
2
)
Relay TRIP 1pL1
Relay TRIP 3ph.
1
)
512
1
)
515
1
)
Device (general) trip command for
breaker pole L1
1
)
BO15 —
2
)—
2
) no pre-setting
2
)
Relay TRIP 1pL2
Relay TRIP 3ph.
513
1
)
515
1
)
Device (general) trip command for
breaker pole L2
1
)
BO16 —
2
)—
2
) no pre-setting
2
)
Relay TRIP 1pL3
Relay TRIP 3ph.
514
1
)
515
1
)
Device (general) trip command for
breaker pole L3
1
)
1
) devices with single- and three-pole tripping
2
) devices with three-pole tripping only
3
) devices with automatic reclosure
Table A-9 Further binary output presettings 7SA6*1*–*B/F/K
and 7SA6*2*–*C/G/L
Binary
Output
LCD Text Function
No.
Remarks
BO2 Breaker (open)
Relay TRIP
2
)
—
511
2
)
Circuit breaker open or
Relay (general) trip command
2
)
BO3 Breaker (close)
AR CLOSE Cmd.
—
2851
3
)
Circuit breaker close or
AR CLOSE Cmd.
3
)
BO4 Breaker (close)
AR CLOSE Cmd.
—
2851
3
)
Circuit breaker close or
AR CLOSE Cmd.
3
)
BO6 Disc.Swit.(open) — Disconnect switch open
BO7 Disc.Swit. (closed) — Disconnect switch closed
BO8 EarthSwit (open) — Earth switch open
BO9 EarthSwit (close) — Earth switch close
BO10 —
2
)—
2
) no presetting
2
)
Relay TRIP 1pL1
Relay TRIP 3ph.
512
1
)
515
1
)
Device (general) trip command for
breaker pole L1
1
)
1
) devices with single- and three-pole tripping
2
) devices with three-pole tripping only
3
) devices with automatic reclosure