3721 3U0>(>) (or Ux) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode 3U0 (or Ux) overvolt-
age
3722 3U0> Voltage Protection 1.0..220.0 V; 30.0 V 3U0> Pickup (or Ux>)
3723 T 3U0> Voltage Protection 0.00..30.00 sec; 2.00 sec T 3U0> Time Delay (or T Ux>)
3724 3U0>> Voltage Protection 1.0..220.0 V; 50.0 V 3U0>> Pickup (or Ux>>)
3725 T 3U0>> Voltage Protection 0.00..30.00 sec; 1.00 sec T 3U0>> Time Delay (or T Ux>>)
3729A 3U0>(>) RESET Voltage Protection 0.50..0.98 0.95 3U0>(>) Reset ratio (or Ux)
3731 U1>(>) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode U1 overvoltage prot.
3732 U1> Voltage Protection 2.0..220.0 V; 150.0 V U1> Pickup
3733 T U1> Voltage Protection 0.00..30.00 sec; 2.00 sec T U1> Time Delay
3734 U1>> Voltage Protection 2.0..220.0 V; 175.0 V U1>> Pickup
3735 T U1>> Voltage Protection 0.00..30.00 sec; 1.00 sec T U1>> Time Delay
3739A U1>(>) RESET Voltage Protection 0.50..0.98 0.98 U1>(>) Reset ratio
3741 U2>(>) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode U2 overvoltage prot.
3742 U2> Voltage Protection 2.0..220.0 V; 30.0 V U2> Pickup
3743 T U2> Voltage Protection 0.00..30.00 sec; 2.00 sec T U2> Time Delay
3744 U2>> Voltage Protection 2.0..220.0 V; 50.0 V U2>> Pickup
3745 T U2>> Voltage Protection 0.00..30.00 sec; 1.00 sec T U2>> Time Delay
3749A U2>(>) RESET Voltage Protection 0.50..0.98 0.98 U2>(>) Reset ratio
3751 Uph-e<(<) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode Uph-e undervoltage
prot.
3752 Uph-e< Voltage Protection 1.0..100.0 V; 0 30.0 V Uph-e< Pickup
3753 T Uph-e< Voltage Protection 0.00..30.00 sec; 2.00 sec T Uph-e< Time Delay
3754 Uph-e<< Voltage Protection 1.0..100.0 V; 0 10.0 V Uph-e<< Pickup
3755 T Uph-e<< Voltage Protection 0.00..30.00 sec; 1.00 sec T Uph-e<< Time Delay
3758 CURR.SUP. Uphe< Voltage Protection ON
OFF
ON Current supervision (Uph-e)
3761 Uph-ph<(<) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode Uph-ph undervoltage
prot.
3762 Uph-ph< Voltage Protection 1.0..175.0 V; 0 50.0 V Uph-ph< Pickup
3763 T Uph-ph< Voltage Protection 0.00..30.00 sec; 2.00 sec T Uph-ph< Time Delay
3764 Uph-ph<< Voltage Protection 1.0..175.0 V; 0 17.0 V Uph-ph<< Pickup
3765 T Uphph<< Voltage Protection 0.00..30.00 sec; 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph
<
Voltage Protection ON
OFF
ON Current supervision (Uph-ph)
3771 U1<(<) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode U1 undervoltage prot.
3772 U1< Voltage Protection 1.0..100.0 V; 0 30.0 V U1< Pickup
3773 T U1< Voltage Protection 0.00..30.00 sec; 2.00 sec T U1< Time Delay
3774 U1<< Voltage Protection 1.0..100.0 V; 0 10.0 V U1<< Pickup
3775 T U1<< Voltage Protection 0.00..30.00 sec; 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1< Voltage Protection ON
OFF
ON Current supervision (U1)
Addr. Setting Title Function Setting Options Default Setting Comments

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals