Appendix
B-39
7SA6 Manual
C53000-G1176-C156-2
3227 >Prot Int 1: Transmitter is switched off
(>PI1 light off)
Protection Inter-
face (Port D+E)
SP ON
OFF
* LED BI BO
3229 Prot Int 1: Reception of faulty datas (PI1
Data fault)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO 93 135 1 GI
3230 Prot Int 1: Total receiption failure (PI1
Datafailure)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO 93 136 1 GI
3233 Device table has inconsistent numbers
(DT inconsistent)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO
3234 Device tables are unequal (DT unequal) Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO
3235 Differences between common parameters
(Par. different)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO
3236 Different PI for transmit and reveive (PI1<-
>PI2 error)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO
3239 Prot Int 1: Transmission time to high (PI1
TT alarm)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO 93 139 1 GI
3243 Prot Int 1: Connected with relay ID (PI1
with)
Protection Inter-
face (Port D+E)
OUT ON
OFF
*
3457 System operates in a closed Ringtopology
(Ringtopology)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO 93 141 1 GI
3458 System operates in a open Chaintopology
(Chaintopology)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO 93 142 1 GI
3464 Communication topology is complete
(Topol complete)
Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO
3487 Equal IDs in constellation (Equal IDs) Protection Inter-
face (Port D+E)
OUT ON
OFF
* LED BO
3541 >Remote Trip 1 signal input (>Remote
Trip1)
Remote Signals SP on
off
* LED BI BO
3542 >Remote Trip 2 signal input (>Remote
Trip2)
Remote Signals SP on
off
* LED BI BO
3543 >Remote Trip 3 signal input (>Remote
Trip3)
Remote Signals SP on
off
* LED BI BO
3544 >Remote Trip 4 signal input (>Remote
Trip4)
Remote Signals SP on
off
* LED BI BO
3545 Remote Trip 1 received (RemoteTrip1 rec) Remote Signals OUT on
off
* LED BO 93 154 1 GI
3546 Remote Trip 2 received (RemoteTrip2 rec) Remote Signals OUT on
off
* LED BO 93 155 1 GI
3547 Remote Trip 3 received (RemoteTrip3 rec) Remote Signals OUT on
off
* LED BO 93 156 1 GI
3548 Remote Trip 4 received (RemoteTrip4 rec) Remote Signals OUT on
off
* LED BO 93 157 1 GI
3549 >Remote Signal 1 input (>Rem. Signal 1) Remote Signals SP on
off
* LED BI BO
3550 >Remote Signal 2 input (>Rem.Signal 2) Remote Signals SP on
off
* LED BI BO
3551 >Remote Signal 3 input (>Rem.Signal 3) Remote Signals SP on
off
* LED BI BO
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation