Appendix
B-46
7SA6 Manual
C53000-G1176-C156-2
3781 DistanceTime Out Forward PICKUP
(Dis.TimeOut Tfw)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 160 2
3782 DistanceTime Out Non-directional
PICKUP (Dis.TimeOut Tnd)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 161 2
3801 Distance protection: General trip (Dis.Gen.
Trip)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 201 2
3802 Distance TRIP command - Only Phase L1
(Dis.Trip 1pL1)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 202 2
3803 Distance TRIP command - Only Phase L2
(Dis.Trip 1pL2)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 203 2
3804 Distance TRIP command - Only Phase L3
(Dis.Trip 1pL3)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 204 2
3805 Distance TRIP command Phases L123
(Dis.Trip 3p)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 205 2
3811 Distance TRIP single-phase Z1
(Dis.TripZ1/1p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 211 2
3813 Distance TRIP single-phase Z1B
(Dis.TripZ1B1p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 213 2
3816 Distance TRIP single-phase Z2
(Dis.TripZ2/1p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 216 2
3817 Distance TRIP 3phase in Z2 (Dis.TripZ2/
3p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 217 2
3818 Distance TRIP 3phase in Z3 (Dis.TripZ3/
T3)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 218 2
3819 Dist.: Trip by fault detection, forward
(Dis.Trip FD->)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 219 2
3820 Dist.: Trip by fault detec, rev/non-dir.
(Dis.Trip <->)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 220 2
3821 Distance TRIP 3phase in Z4 (Dis.TRIP 3p.
Z4)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 209 2
3822 Distance TRIP 3phase in Z5 (Dis.TRIP 3p.
Z5)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 210 2
3823 DisTRIP 3phase in Z1 with single-ph Flt.
(DisTRIP3p. Z1sf)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 224 2
3824 DisTRIP 3phase in Z1 with multi-ph Flt.
(DisTRIP3p. Z1mf)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 225 2
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation