Appendix
B-49
7SA6 Manual
C53000-G1176-C156-2
4166 Power Swing TRIP command (Pow. Swing
TRIP)
Power Swing OUT ON ON LED BO 29 166 1
4167 Power Swing detected in L1 (Pow. Swing
L1)
Power Swing OUT ON
OFF
ON
OFF
LED BO
4168 Power Swing detected in L2 (Pow. Swing
L2)
Power Swing OUT ON
OFF
ON
OFF
LED BO
4169 Power Swing detected in L3 (Pow. Swing
L3)
Power Swing OUT ON
OFF
ON
OFF
LED BO
4203 >BLOCK Weak Infeed Trip function
(>BLOCK Weak Inf)
Weak Infeed (Trip
and/or Echo)
SP * * LED BI BO
4221 Weak Infeed Trip fct. is switched OFF
(WeakInf. OFF)
Weak Infeed (Trip
and/or Echo)
OUT ON
OFF
* LED BO 25 21 1 GI
4222 Weak Infeed Trip function is BLOKKED
(Weak Inf. BLOCK)
Weak Infeed (Trip
and/or Echo)
OUT ON
OFF
ON
OFF
LED BO 25 22 1 GI
4223 Weak Infeed Trip function is ACTIVE
(Weak Inf ACTIVE)
Weak Infeed (Trip
and/or Echo)
OUT * * LED BO 25 23 1 GI
4231 Weak Infeed Trip function PICKED UP
(WeakInf. PICKUP)
Weak Infeed (Trip
and/or Echo)
OUT *
OFF
LED BO 25 31 2 GI
4232 Weak Infeed Trip function PICKUP L1 (W/I
Pickup L1)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO
4233 Weak Infeed Trip function PICKUP L2 (W/I
Pickup L2)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO
4234 Weak Infeed Trip function PICKUP L3 (W/I
Pickup L3)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO
4241 Weak Infeed General TRIP command
(WeakInfeed TRIP)
Weak Infeed (Trip
and/or Echo)
OUT * * LED BO 25 41 2
4242 Weak Infeed TRIP command - Only L1
(Weak TRIP 1p.L1)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO 25 42 2
4243 Weak Infeed TRIP command - Only L2
(Weak TRIP 1p.L2)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO 25 43 2
4244 Weak Infeed TRIP command - Only L3
(Weak TRIP 1p.L3)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO 25 44 2
4245 Weak Infeed TRIP command L123 (Weak
TRIP L123)
Weak Infeed (Trip
and/or Echo)
OUT * ON LED BO 25 45 2
4246 ECHO Send SIGNAL (ECHO SIGNAL) Weak Infeed (Trip
and/or Echo)
OUT ON ON LED BO 25 46 2 GI
4247 ECHO Tele.Carrier RECEPTION, Device1
(ECHO Rec. Dev1)
Echo Receive
over Protection
Interface
OUT ON
OFF
ON LED BO
4248 ECHO Tele.Carrier RECEPTION, Device2
(ECHO Rec. Dev2)
Echo Receive
over Protection
Interface
OUT ON
OFF
ON LED BO
4249 ECHO Tele.Carrier RECEPTION, Device3
(ECHO Rec. Dev3)
Echo Receive
over Protection
Interface
OUT ON
OFF
ON LED BO
4253 >BLOCK Instantaneous SOTF Overcur-
rent (>BLOCK SOTF-O/C)
Instantaneous
HighSpeed SOTF
Overcurrent
SP * * LED BI BO
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation