2.14 Temperature Detection via RTD Boxes
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
200
2.14 Temperature Detection via RTD Boxes
Up to two temperature detection units (RTD-boxes) with 12 measuring sensors in total can be applied for tem-
perature detection and are recognized by the protection device.
Applications
In particular the RTDs enable the thermal status of motors, generators and transformers to be monitored.
Rotating machines are additionally monitored for a violation of the bearing temperature thresholds. The tem-
peratures are measured in different locations of the protected object by employing temperature sensors
(RTD = Resistance Temperature Detector) and are transmitted to the device via one or two 7XV566 RTD-
boxes.
2.14.1 Description
RTD-box 7XV56
The RTD-box 7XV566 is an external device mounted on a standard DIN rail. It features 6 temperature detectors
and one RS485 interface for communication with the protection device. The RTD-box detects the coolant tem-
perature of each measuring point from the resistance value of the temperature detectors (Pt 100, Ni 100 or Ni
120) connected via two- or three-wires and converts it to a numerical value. The numerical values are made
available at a serial port.
Communication with the Protection Device
The protection device can employ with up to 2 RTD-boxes via its service port (port C).
Therefore, up to 12 temperature measuring points are available in this way. For greater distances to the pro-
tection device the communication via fiber optic cables is recommended. Alternative communication structures
are shown in Appendix A.3.
Processing Temperatures
The transmitted raw temperature data is converted to a temperature in degrees Celsius or Fahrenheit. The con-
version depends on the temperature sensor used.
For each temperature detector two threshold decisions can be performed which are available for further pro-
cessing. The user can make the corresponding allocations in the configuration matrix.
Each temperature input issues an alarm in case of a short-circuit or an interruption of the sensor circuit or if a
sensor is configured but not assigned. Additionally, a group annunciation is generated via all 6 temperature
inputs of an RTD-box (14101 „Fail: RTD“). In case of a communication fault, an alarm of the entire RTD-
box is issued (264 „Fail: RTD-Box 1“ or 267 „Fail: RTD-Box 2“).
The following figure shows the logic diagram for temperature processing.
The manual supplied with the RTD-box contains a connection diagram and dimensioned drawing.