EasyManua.ls Logo

Siemens SIPROTEC 7SJ61 - High-Impedance Ground Fault Unit Protection

Siemens SIPROTEC 7SJ61
454 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.4 Single-Phase Overcurrent Protection
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
85
2.4.2 High-impedance Ground Fault Unit Protection
Application Examples
In the high-impedance procedure, all CT's operate at the limits of the protected zone parallel on a common,
relatively high-resistive resistor R whose voltage is measured.
The CTs must be of the same design and feature at least a separate core for high-impedance protection. In
particular, they must have the same transformer ratios and approximately identical knee-point voltage.
With 7SJ61, the high-impedance principle is particularly well suited for detecting ground faults in grounded net-
works at transformers, generators, motors and shunt reactors.
Figure 2-21 shows an application example for a grounded transformer winding or a grounded motor/generator.
The right-hand example depicts an ungrounded transformer winding or an ungrounded motor/generator where
the grounding of the system is assumed somewhere else.
Figure 2-21 Ground fault protection according to the high-impedance principle
Function of the High-Impedance Principle
The high-impedance principle is explained on the basis of a grounded transformer winding.
No zero sequence current will flow during normal operation, i.e. the starpoint current is I
SP
= 0 and the phase
currents are 3 I
0
= I
A
+ I
B
+ I
C
= 0.
In case of an external ground fault (left in Figure 2-22), whose fault current is supplied via the grounded star-
point, the same current flows through the transformer starpoint and the phases. The corresponding secondary
currents (all current transformers have the same transformation ratio) compensate each other; they are con-
nected in series. Across resistor R only a small voltage is generated. It originates from the inner resistance of
the transformers and the connecting cables of the transformers. Even if any current transformer experiences a
partial saturation, it will become low-ohmic for the period of saturation and creates a low-ohmic shunt to the
high-ohmic resistor R. Thus, the high resistance of the resistor also has a stabilizing effect (the so-called resis-
tance stabilization).

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ61

Related product manuals