2.15 Phase Rotation
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
210
2.15.2 Setting Notes
Setting the Function Parameter
The normal phase sequence is set at 209 (see Section 2.1.3). If, on the system side, phase rotation is reversed
temporarily, then this is communicated to the protective device using the binary input ā€ž>Reverse Rot.ā€œ
(5145).