In conjunction with the power system control several command types can be distinguished for the device:
2.18.2.1 Description
Commands to the System
These are all commands that are directly output to the switchgear to change their process state:
Switching commands for the control of circuit breakers (not synchronized), disconnectors and ground elec-
trode,
Step Commands, e.g. raising and lowering transformer LTCs
Setpoint commands with configurable time settings, e.g. to control Petersen coils
Internal / Pseudo Commands
They do not directly operate binary outputs. They serve to initiate internal functions, simulate changes of state
or to acknowledge changes of state.
Manual overriding commands to manually update information on process-dependent objects such as indi-
cations and switching states, e.g. if the communication with the process is interrupted. Manually overridden
objects are flagged as such in the information status and can be displayed accordingly.
Tagging commands (for "Setting") for internal object information values, e.g. deleting / presetting switching
authority (remote vs. local), parameter set changeovers, data transmission blockage and metered values.
Acknowledgment and resetting commands for setting and resetting internal buffers or data states.
Information status command to set/reset the additional "information status" of a process object, such as:
Input blocking
Output Blocking