Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
284
3.1.3.3 Panel Flush Mounting
For installation proceed as follows:
Secure the device to the panel with four screws. For dimensions see the Technical Data, Section 4.22.
Connect the robust low-ohmic protective ground or station ground to the grounding terminal on the rear plate
of the device. The cross-sectional area of the cable used must correspond to the maximum connected cross-
section, but must be at least 2.5 mm
2
.
Alternatively, fasten the said ground to the grounding surface on the side with at least one M4 screw.
Connections according to the circuit diagram via screw terminals, connections for optical fiber cable and
electrical communication modules via the housings. The SIPROTEC 4 System Description provides infor-
mation regarding maximum wire size, torque, bending radius and cable relief and must be observed.