Mounting and Commissioning
3.2 Checking Connections
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
289
Connect an ammeter in the supply circuit of the power supply. A range of about 2.5 A to 5 A for the meter is
appropriate.
Switch on m.c.b. for auxiliary voltage (supply protection), check the voltage level and, if applicable, the po-
larity of the voltage at the device terminals or at the connection modules.
The current consumption should correspond to the power input in neutral position of the device. The mea-
sured steady state current should be insignificant. Transient movement of the ammeter merely indicates the
charging current of capacitors.
Remove the voltage from the power supply by opening the supply circuit of the power supply.
Disconnect the measuring test equipment; restore the normal power supply connections.
Check the trip and close circuits to the power system circuit breakers.
Verify that the control wiring to and from other devices is correct.
Check the signalling connections.
Remove the voltage from the power supply by closing the supply circuit of the power supply.