SITRANS FM100
page 60 A5E48762204-AA
Index
[hex]
Name
Description
Factory default
Max Value
Min Value
Length
[Bytes]
Data Type
Access
0x0123
OUT1Analog
NamurStandard
If enabled (1) the
analogoutput
conforms with the
NAMUR Standard
NE42. If disabled
(0) the
analogoutput stays
in his equivalent
range (e.g. 4-
20mA)
1
(0) - NAMUR disabled
(1) - NAMUR enabled
1
UIntegerT
R/W
0x0124
OUT1AnalogValue
0mA
The value from the
slot used for the
0mA scaling point
0,0
OUT1Analog
Value20mA
MRS
4
FloatT
R/W
0x0128
OUT1AnalogValue
4mA
The value from the
slot used for the
4mA scaling point
0,0
OUT1Analog
Value20mA
MRS
4
FloatT
R/W
0x012C
OUT1AnalogValue
20mA
The value from the
slot used for the
20mA scaling point
100,0
MRE
OUT1Analog
Value0mA
4
FloatT
R/W
0x0130
OUT1AnalogValue
0V
The value from the
slot used for the
0V scaling point
0,0
OUT1Analog
Value10V
MRS
4
FloatT
R/W
0x0134
OUT1AnalogValue
2V
The value from the
slot used for the
2V scaling point
0,0
OUT1Analog
Value10V
MRS
4
FloatT
R/W
0x0138
OUT1AnalogValue
10V
The value from the
slot used for the
10V scaling point
100,0
MRE
OUT1Analog
Value0V
4
FloatT
R/W
0x013C
OUT1PulseVolume
The volume
represented by
one pulse
1,0
999,9
0,0
4
FloatT
R/W
0x0140
OUT1PulseVolume
Unit
Unit used for the
pulse output
1
(0) - USER
(1) - L
(2) - mL
(3) - m3
(4) - galUS
(5) - galUK
(6) - Barrel
1
UIntegerT
R/W
0x0141
OUT1PulseVolume
UnitUser
User Unit used for
the pulse output
1,0
9999,9
0,0
4
FloatT
R/W
0x0145
OUT1PulseWidth
Width of each
pulse
1
20000
1
2
UIntegerT
R/W